Flueet — Chimney flue sizing, draught and liner choice | flueet.com

Stove flue sizing

Flueet — Chimney flue sizing, draught and liner choice | flueet.com

What this guide is

An independent reference on flue sizing, draught measurement and liner ratings, built from published standards, building regulations and the sizing rules manufacturers apply across their ranges.

What it is not

Not a design service, not a product shop, and not a substitute for a site-specific assessment by a competent installer or building control body.

125-150 mminternal flue diameter for most sealed wood stoves
4-6 Paminimum draught at the outlet of a sealed stove
3× diameterclearance to combustibles for single-wall stove pipe

Start with the outlet, not the brochure

A sealed stove's chimney must be at least as big as the appliance outlet — roughly 100-130% of the outlet area.

Every stove leaves the factory with a flue outlet of a fixed diameter, and that outlet is the one measurement you may not go below. A chimney that necks down past the outlet throttles the appliance: smoke spills on lighting, the glass tars up and draught readings sag.

The working rule is that the flue run should carry 100-130% of the outlet's cross-sectional area, all the way from the stove collar to the terminal. A modest increase above the outlet is normal practice; a decrease is not.

Only after the outlet is satisfied does output in kilowatts come into play, because output is what pushes you from one standard diameter to the next.

The signature mark of this site, drawn as a plate

Match the diameter to the kilowatts

For insulated twinwall, 125 mm covers about 5-8 kW and 150 mm covers about 8-12 kW; open fires run 175-200 mm.

Manufacturers converge on the same bands because flue gas volume tracks heat output. A 5 kW room heater and a 10 kW stove do not move the same amount of smoke, and the flue has to move all of it without throttling the fire.

Oversizing is not a free pass either. A very large flue on a small stove lets gases cool and slow before they reach the terminal, which is why the bands are bands rather than minimums.

Open fires sit outside this logic: with no sealed outlet to match, they are sized from the fireplace opening instead, and normally land on liners of 175-200 mm.

The signature mark of this site, drawn as a plate

Flue sizing at a glance

The working figures for sizing, rating and placing a wood-stove flue.
Appliance and dutyOutput or positionFlue size or limitThe check behind it
Sealed wood stove5-8 kW125 mm internal diameterDraught 4-6 Pa at the outlet
Sealed wood stove8-12 kW150 mm internal diameterDraught 4-6 Pa at the outlet
Open fireopening area sets the size175-200 mm diameterFlue area 12-20% of the opening
Single-wall stove pipe125 mm diameter375 mm clearance to combustiblesClearance equals three times diameter
Insulated twinwall125-150 mm diameter50-65 mm clearanceManufacturer's stated distance
Chimney terminalmore than 2.3 m from a boundaryat least 1 m above groundUK Approved Document J
Chimney terminalwithin 2.3 m of a boundaryat least 2.1 m above groundUK Approved Document J
Liner for wood serviceEN 1856-1 designationT400 N1400 °C continuous, 600 °C soot-fire peak, 20 Pa
The working figures for sizing, rating and placing a wood-stove flue.

Terms used on this page

Flue
The passage that carries combustion gases from the appliance to the open air. Its internal cross-section, not its outside casing, is what sizing rules refer to.
Twinwall flue
A factory-made insulated metal chimney with an inner liner and an outer casing separated by insulation. Sold in standard internal diameters such as 125 mm and 150 mm.
Draught
The negative pressure a chimney develops, measured in pascals at the appliance outlet with a manometer or digital draught gauge.
EN 1856-1
The European standard for factory-made metal chimneys. Its designation codes temperature class and pressure rating, for example T400 N1.
Terminal
The top of the chimney where flue gases discharge. Its height above ground and its distance from boundaries are fixed by building regulations.
Clearance to combustibles
The minimum distance between a flue pipe and any material that can burn. Three times the pipe diameter for single-wall pipe, far less for insulated twinwall.

Prove it with a draught reading

Draught is measured at the appliance outlet in pascals: 4-6 Pa minimum for a sealed stove, 5-10 Pa for an open fire.

A manometer or digital draught gauge connected at the appliance outlet tells you whether the chimney is actually pulling. The reading is taken with the fire established and the flue warm, not on a cold chimney at first light.

Below 4 Pa on a sealed stove the fire will be hard to light, prone to smoking back and lazy to respond to the air controls. An open fire wants a little more — 5-10 Pa — because it has no sealed door to shape the airflow.

If the number falls short, the cause is almost always one of five things: a flue too small for the outlet, a run with too many bends, a terminal sitting too low, a soot restriction, or a room too airtight to feed the fire. Each cause is worked through in the draught guide linked below.

Sources and standards

The figures cited on this page trace to EN 1856-1, UK Approved Document J, Ecodesign requirements for solid-fuel stoves and standard sweeping practice.